GasQuip FLEX SF₆ Analysis Report
Pass
Test Nametest data
Technicianjbj
Location / Assetjhb
Standard: IEC 60480 · Reuse SF₆
SF₆ ≥ 97.0%
H₂O ≤ 200 पीपीएमवी
SO₂ ≤ 12 पीपीएमवी
Pass
SF₆ Purity 100.0 % Volume Pass
Moisture (H₂O) 115 पीपीएमवी Pass
SO₂ 0 पीपीएमवी —
O₂ — % Volume Input Start 37.37 PSI
Input End 36.67 PSI
Δ Pressure −0.70 PSI
or
Conditions at time of test
Temperature — °F
Humidity — %
Baro. Pressure — hPa
Coordinates —